OVERVIEW - Engineer’s Specification
The Harrington Signal HMX system shall include one Master Panel and one or more
Distributed Panels. The system shall be microprocessor based, and shall be compatible for
use with contact closures from the Fire Alarm Control Panel, (FACP). The system shall have
a high-speed communication bus and have the capacity for 6 channels of combined audio
and data on a single pair of wires. The field wiring for the communication bus may be
configured for either Style 4 or Style 7 supervision. The system shall have the capacity for
Fire Fighters Phone communication. The system shall have a minimum capacity of 2048
monitor and control points.
The Master Panel shall contain an integral microphone, dual channel digital message
repeater, (DMR) and digital tone generator, 120 VAC power supply, and battery charger. The
system shall be modular in design, and shall be expandable such that additional system
control points may be configured. The system shall include integral self-diagnostic routines
that shall continually monitor system status, and shall indicate the precise type of trouble
conditions should they occur in the system. A trouble condition within the system shall cause
a trouble indication to be transmitted to the FACP.
Distributed panels shall provide a minimum of 4 Class "B" (Style Y) speaker circuits,
expandable to eight total. Alternately, panel may be configured for 4 Class "A" (Style Z)
speaker circuits. Panel will provide up to 6 simultaneous audio channels, up to 16 Fire
Phone circuits. Amplifiers will contain their own power supplies, battery chargers and provide
auxiliary power for other components. Speaker circuits shall be supervised for short and open
circuit conditions, and shall be able to withstand transient or continuous short-circuit
conditions without damage to the system.
System may be configured for General Alarm All Call operation, Alarm by Zone or
Floor Above / Floor Below as required. Contact closures shall allow immediate broadcast of
an alarm signal and evacuation message to the appropriate area. Non-Alarm areas may
receive alert tones and messages as required or activated by the FACP.
The alarm signal/evacuation message shall be broadcast until the FACP is reset, or until
emergency personnel interrupt the broadcast with a manual page.
To prevent unauthorized tampering, the voice evacuation system shall disable the
microphone if the microphone is keyed continuously for 3 minutes or more. Systems that do
not have this feature shall not be acceptable.
P/N HS-5010 REV. C
page 1 of 12
2519 Fourth Avenue
Moline, IL 61265
(800) 577-5758 (v)
(309) 762-8215 (f)
www.harringtonfire.com
Vue de la page 0
1 2 3 4 5 6 ... 11 12

Résumé du contenu

Page 1 - Installation Instructions

Harrington Signal HMX Installation InstructionsOVERVIEW - Engineer’s SpecificationThe Harrington Signal HMX system shall include one Master Panel and

Page 2 - BATTERY MAINTENANCE

P/N HS-5010 REV. Cpage 10 of 12 Component Measured Voltage DC to Chassis Ground Resistance Range to cause Ground Fault in Standby (measured in 5K inc

Page 3 - System Operation

MBRConnection DetailTerminal DesignationTB-11 Strobe Connection (if used)J9 - right 2 rows “shorted” class B speaker circuits left 2 rows “sho

Page 4 - “GLOBAL RESET”:

HMX SpecificationsCommunications Bus: The communications bus conforms to the RS-485 standard and requires the use of UTP- cable for 1M Baud data rates

Page 5 - Typical System Layout

INSTALLATIONInstaller must insure that all wiring and devices installed in system meet the following standards: National Electrical Code (NFPA 70) NFP

Page 6 - Controls and Displays

System Operation **Note** ALL panels in system are pre-programmed at the factoryAlarm When an input on the MX-II FACP Interface card is pulled down to

Page 7 - Distributed Panel Wiring

HMX Control Panel Refer to Master Panel Controls and Display diagram (Page 6). The Control Panel status indicators are 'Alarm', 'Fault&

Page 8 - Terminal Designation

PAGING CONTROLFIRE PHONE CONTROL Harrington Signal HMXTrue Multiplex SystemTypical System LayoutNetComm Loop:Unshielded Twisted Pair, Single pair18/2

Page 9 - (N.O. Dry Contact)

HMX CONTROLFIRE PHONE CONTROLAlarmFaultPowerPaging MicrophoneMessage Display System ResetFault SilencePaging All-CallLamp TestFunctionSwitches & L

Page 10 - (measured in 5K increments)

P/N HS-5010 REV. Cpage 7 of 12All wiring with exception of120 VAC and Battery Connection is Power-Limited.Route AC power and Batterywires to bottom-l

Page 11 - NetCom Bus

P/N HS-5010 REV. Cpage 8 of 12TB1 TB2TB3 TB4 TB5P1P2P3P4J1123LED3LED2LED1DCCMaster Panel DCCConnection DetailTerminal Designation1 - Earth (Chassis)2

Page 12 - HMX Specifications

MX-II / PWRConnection DetailTerminal DesignationWiringFACP Bell Circuit - #18 AWG.Input Control - #24 AWG.(Must be in the same room within 20 feet o