Harrington-signal HAVE 100 Manuel d'utilisateur

Naviguer en ligne ou télécharger Manuel d'utilisateur pour Panneau de contrôle Harrington-signal HAVE 100. Harrington Signal HAVE 100 User Manual Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 9
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
TheEVAX25/EVAX50/EVAX100isaselfcontainedamplifier,tonegenerator,digitalmessagerepeaterandsupervisory
interface.ItisdesignedtobeusedinconjunctionwithaUL listedFire AlarmControlPanel(FACP)toprovideaListedVoice
Evacuation AlarmSystem.
TheFACP providesallinitiatingcircuitryandasignalingcircuittotheEVAX25/EVAX50/EVAX100. TheEVAX25/EVAX50
/EVAX100providesitsowninternalsupervisionaswellassupervisionforitsspeakerlines. Anyfaultisreportedbacktothe
FACP.InnormalstandbythesupervisorycircuitfromthepanelisconnectedtoamatchingEOLR.ShouldtheEVAX25/
EVAX50EVAX100sufferaninternalfailureorshouldtherebeanyfaultonthespeakerlineacontactwouldopenandthe
FACP wouldreportitasanopenfaultforthatcircuit.
TheEVAX25/EVAX50/EVAX100isdesignedtobepoweredfrom120VACat60Hz. TheEVAX25willprovide25Wto
thespeakercircuit. TheEVAX50willprovide50W .Speakersmaybe25or70VRMS
(jumperselected,25Visfactoryset).
I
Installermustinsurethatallwiringanddevicesinstalledinsystemmeetthefollowingstandards:
NationalElectricalCode(NFPA 70)
NFPA Standard72
LifeSafetyCode(NFPA 101)
Installequipmentinaclean,dryenvironment,avoidinstallationwhereequipmentcouldbesubjectedtovibration.
Removeelectronicassembliesfromtheenclosurepriortoanydrillingorpunchingoftheenclosure.Wherepossible,
makeallcableentriesfromtherearorsides.Beforemakinganymodificationstotheenclosure,becertainthatthey
willnotinterferewithassembliesorbatteries.
(Refertowiringandterminaldesignationdiagrams)
1.Connectspeakerlinesto TB1-5(+)&6(-),observepolarityandinsureallspeakersareconnectedlikewise.
ForClass"A"(Style"Z")thereturnsare TB1-7(-)&8(+).
2.InsurethatthemicrophoneisattachedtoconnectorP2.IfMicrophoneisnotinstalledinsurethatswitchSN2-8is
intheOFFposition.
5.Connect120VAC,60Hz,powertotheblackandwhitepigtailleadsfromtransformerprimary.
Securegroundleadtogroundingstudincabinet.
6.Oncepowerisontotheunit,connectbatterywiringharness,Red(+)/Black(-). .Minimumbattery
sizeis24V7AHr.Maximumbatterysizeis18AhronEvax25/50&24AhronEvax100.(use212Vbatteriesconnectedin
series,seetypicalinstallationdiagram).Iftheunitdoesnothaveitsownbatteriesandreliesonanexternalpowersupply
withbatteryback-up,insurethatswitchSN2-7isintheOFFposition. WiringforbatteriesisNonPower-Limited.
CaremustbetakentoinsurethatallPower-Limitedwiringmaintainaminimumspacingof¼"fromanyNonPower-Limited
wiring.Ifbatteriesmustbelocatedinseparateenclosure,provideseparateconduitrunforbatterywiringonly.
Onceallpowerandcircuitsareconnected,theGreenLEDwillremainontoindicatethattheEVAX25/EVAX50/
EVAX100isfullyoperationalandallcircuitsarenominal.
TheEVAX100willprovide100W.
NSTALLATION
WIRING
Observepolarity
NOTE:
3. AttachtheappropriateEOLRfortheFACP to TB3-3&4and TB3-5&6. The TB3term5&6valuemustbeplacedatthe
endofthespeakerlineaswell. YoumustuseEOLRvalueasspecifiedintheFACP manufacturesinstallationinstructions
fortheindicatingappliancecircuit.Note:ifyoursystemincludesoneormoreEVX-4Zzonesplitters,theFACP
EOLRisrelocated.SeeEVX-4ZinstallinstructionsP/N1-5010RevC.
4.ConnectFACP signalingcircuitto TB1-3(+)&4(-), AlarmPolarity(alarmpolarityisshown).
EVAX25/EVAX50/EVAX100
VOICEEVACUATIONINTERFACESYSTEM
INSTALLATIONINSTRUCTIONS
P/N1-5001REV.G
Page1of8
HARRINGTON
FIREALARM
SIGNALINC.
ISO9001Certified
25194th AvenueMoline,IL 61265
(309)762-0731FAX(309)762-8215
www.harringtonsignal.com
Vue de la page 0
1 2 3 4 5 6 7 8 9

Résumé du contenu

Page 1 - EVAX25/EVAX50/EVAX100

TheEVAX25/EVAX50/EVAX100isaselfcontainedamplifier,tonegenerator,digitalmessagerepeaterandsupervisoryinterface.Itisdesignedtobeu

Page 2

EVAX25/EVAX50/EVAX100TERMINAL DESIGNATIONSTB1:1414TER1&2TER3&4TER5&6-PowerInput24-32V AC/DC(NOTE , )-FACP Signal

Page 3 - FIREALARM

OPTIONS:AUX+24VDCOUTPUTDonotCONNECTIONOF AN AUX AUDIOSOURCEOPTIONAL SUPERVISORY CIRCUIT- TB2-4,8,9&10Theseterminalsprovideamax.200mA

Page 4 - EVAX25/50/100

+FIREEOLEOLRFIREFIREFIREFIREEOL5 6 7 8TB1StandardLifeSafetySpeakers,StrobesconnectedandpoweredseparatelyBreakwiretomaintainsupervision.Do

Page 5

EVAX25/50/100OPTIONAL SUPERVISORYCIRCUIT APPLICATION+EOLZONEEOLREOLMATCHINGEOLR(SPEAKERCIRCUIT)Supervised-PowerLimitedSIGNALCIRCUITALARMPOLAR

Page 6

TB11 2 345 6 7 8TB312345678TB212345678910111 2 3J2EVAX25/50/100AUX AUDIOENABLECONNECTIONDETAILCustomerProvidedDryContactN.O.Aux AudioInputAux

Page 7

EVAX25/50/100SWITCHSETTINGSON=1(DOWN)OFF=0(UP)SwitchNetworkDetail1 8SN1Default=0/1/0/1/0/1/0/1SW1/2/3 Setstheinitialdelay

Page 8 - R3(SeeNOTE2)

EVAX25/50/100SIGCKTFACP EOLR33456456R1R2R1 (SeeNOTE1)EndoflineresistorforFACP SignalCircuit.NOTE1:IftheFire AlarmSignalCircuitrequ

Modèles reliés HAVE 50 | HAVE 25 |

Commentaires sur ces manuels

Pas de commentaire